Blocked Rotor

Question:  The Magna screen says the pump is blocked, error code 51. How do I fix it?

Answer:  The first step is to remove the pump head by loosening the steel collar.

 

Once removed, inspect the volute for any debris. Next is to pull off the can and clean off the magnet. This step is often missed because most are not aware that it can be removed.

 

 

 